SPECIFICATION - STANDARD CASE - SQ / RD / RT & OIFRP SERIES CASE COOLING
TOWERS
-
COOLING CAPACITY:
The tower series CASE-SQ & OIFRP, designed to cool from the smallest
to the largest flow-rate of water and varying conditions, providing
there are no restrictions or limitations of air to, through and from
the cooling tower.
-
DESIGN:
The cooling tower is of counter flow design with PVC fill media or
HDPE balls with air being induced from air inlets, induced mechanical
draft, vertical air discharge, pipe distribution of the water employing
a single fan.
-
CONSTRUCTION:
The framework is fabricated from FRP designing to carry the mechanical
equipment water in the spray arms, live and wind loads. Operational
and wind loads up to 200 km/hr of protected area can be carried in
any horizontal direction.
-
CASING:
The casing is flame-retardant, chemical resistance gel-coat, single/multiple
formed fiberglass UV stabilized panels.
-
FAN CYLINDER, FAN DECK:
Fibreglass bell mouth fan cylinder UV stabilised. Fan deck is fabricated
from FRP.
-
UNITIZED STEEL TO SUPPORT MECHANICAL EQUIPMENT:
The complete supporting structure is Hot Dip Galvanised (HDG) to prevent
any kind of corrosion.
-
WATER DISTRIBUTION:
System comprises a main header with perforated branch arms or rotating
HDPE branch pipes.
-
COLD WATER BASIN:
The standard tower is provided with single FRP cold water basin and
single set of plumbing fittings. Cold water floor is also FRP. Galvanised
fitting includes an overflow, drain and screened depressed sump. (Depends
on scope of work) Water make up valve is of brass sufficient to make
up for bleed and evaporation (Depends on scope of work) .
-
FILL MEDIA:
Is PVC or HDPE with extra rigidity, of size 24X 12 X 6 feet cubed,
These are easily handled in construction and maintenance. Fill media
is vertical flute type with multiple leading edges to ensure laminar
water film. Fluted helical spirals are incorporated to eliminate the
danger of air coring or liquids hold ups. An option of High Density
PolyEthylene (HDPE) is available for high water temperatures.
-
FANS:
Induced draft axial flow fan is of aerofoil section adjustable pitch.
Material could be of FRP/Aluminium. Fan can be assessed from the top
of the Cooling Tower for any maintenance or clearing purpose.
-
ELECTRIC MOTORS:
flange mounted single speed TEFC weatherproofed IP55 rated, 3 phase
50 Hz cycle 415 volt 6 pole/8 pole.
-
HARDWARE:
Stainless steel bolts, nuts and washers.
-
PROTECTIVE COATINGS:
All sheet parts not otherwise mentioned are HDG after fabrication
to all code requirements.
-
CONSTRUCTION AND PERFORMANCE:
In accordance with the drawings and information provided. It is the
purchaser’s responsibility to ensure that the equipment conforms in
every respect with any tender specifications binding upon or accepted
by the purchaser. No responsibility therefore or arising therefrom
is accepted by Composite Aqua Systems & Equipments Pvt. Ltd.
-
SITING OF THE COOLING TOWER:
The cooling tower is designed to operate effectively when so sited
as to enable it to have an uninhibited flow of clean air of the designing
condition and volume to through and from it. The siting of the cooling
tower is the entire responsibility of the purchaser. Composite Aqua
Systems & Equipments Pvt. Ltd., shall have no liability or responsibility
for incorrect siting or for siting carried out otherwise than in accordance
with its specific advice. Advice as to siting of the cooling tower
will be made available to the purchaser if requested for a reasonable
fee.
-
QUALITY AND PERFORMANCE IMPROVEMENT:
In line with continual development, this specification and all dimensions
are subject to change without notice.
-
VIBRATION AND SOUND LEVELS:
No levels are specified or guaranteed in this specification. Standard
sound criteria are available on request for the cooling tower manufactured
as standard by Composite Aqua Systems & Equipments Pvt. Ltd.
-
SPARE PARTS:
Available on request from our works.
-
EXCLUSIONS:
Only those items detailed in the specification will be supplied with
standard model cooling tower.
-
ILLUSTRATIVE BROCHURE :
Issued for information and illustrative purpose only. Subject to change
and re-issue at the discretion of Composite Aqua Systems & Equipments
Pvt. Ltd.
..Back

|